냉매 충진량에 따른 냉동시스템의 성능 예측
이경중, 방광현 · 1999
A theoretical model for the transient performance of vapor-compression air-conditioning system has been developed to evaluate the influence of the refrigerant charge on the system performance. A set of mass and energy equations for the heat exchangers and the capillary tube and an appropriate model for the compressor are solved numerically. For a system charged with 750 gram of R-22 refrigerant and for indoor air of 27℃ and outdoor air of 35℃, the present model successfully predicts the transient behavior of the vapor-compression air-conditioner from the startup. At the steady-state, about 90% of the refrigerant mass is distributed in the condenser and the liquid line. As the refrigerant charge is increased, both the evaporating and condensing pressures increase gradually, but the cooling rate and the COP show a maximum in the range of 750-800 grams of refrigerant charge. This amount of refrigerant mass is determined to be the optimum charge of the model system.