히트펌프 조건 시 휜-관 위의 착상에 관한 연구

윤신혁, 조금남, 하야세 가쿠 · 대한설비공학회 학술발표대회논문집 · 2009

The present study measured the frost thickness and frost mass on a flat plate and on a circular tube to propose the correlation equations for the local and average frost thickness, frost density, and frost mass. Key parameters were the cooling surface temperature, absolute humidity of air, air temperature, and air velocity. A 50% ethylene glycol aqueous solution was applied as a coolant. The correlation equations for the frost thickness and mass of the flat plate and circular tube were proposed. They utilized topredict the frost thickness and mass of the simple fin and tube. The predicted local and average frost thicknesses and masses were compared with the measured values for the simple fin and tube. The local frost thickness on the fin decreased along the air flow direction. The predicted frost thickness agreed with the measured data within 5% while the predicted frost mass agreed with the measured data within 10%. The methodology to predict the frost for the simple fin and tube was developed and proposed.