대심도 역사 승강장 화재 시 승강장 환기 운전 모드에 대한 고찰

장용준, 류지민 · 한국철도학회 학술발표대회논문집 · 2013

The validity of the ventilation operation modes for platform fire in the deeply underground subway station has been investigated. Shingumho station(The line # 5, Depth: 46m) has been selected as a simulation model. Currently ventilation operation mode in Shingumho-station platform has been set up as a full exhaust mode in case of platform fire. In this study, two kinds of ventilation mode were analyzed by comparing an entire exhaust mode with an entire supply mode in platform fire. Ventilation diffusers were modeled as the 222 square shapes of 0.6m(x)X0.6m(y) and the 4 rectangular shapes of 1.2m(x)X0.8m(y). The whole station was covered for this analysis and total of 7.5 million grids were generated for this simulation. In order to enhance the efficiency of calculation, parallel processing by MPI was employed and Large Eddy Simulation method in FDS code was adopted.