급수 사용량 분석을 통한 급수설계 부하 평가
오병길, 김원석, Byung Seok Lee · 대한설비공학회 2015년도 하계학술발표대회 · 2015
There is lots of other country and comparison water use while as to korea, the water resource is not aboundant. we calculate the amount of water consumption appropriate and apply from a design for the economize water. It is unconverted, the water use design method of korea is using the former standard. In spite of using the water saving sanitation faucet and closet. The toilet bowl 1 time water use is using a product in 15 lpm products less than 6 lpm at present. Now the washbowl 6 lpm, kitchen sink 6 lpm, and shower head 7 lpm is used. In this study intended for APT usage of water hourly and analyzed by day of the week.and we found that the flow rate of 50% to 60% of design flow in the summer peak water usage analysis using a APT use. That the data accumulation and analysis of the patterns of water use and consumption continue to design and configure a system close to being fodder consumption will save on water resources and transportation of energy
Cited by 0 works.