히트펌프 증발기의 착상 예측을 위한 핀-관 모델에서의 국부 서리 물성치와 서리성장에 관한 연구
곽동근, 이윤석, 조금남 et al. · 대한기계학회 춘추학술대회 · 2010
The present study measured the frost characteristics on an array of fin-tube under the heat pump condition. The key parameters were air temperature from 2 to 7℃, absolute humidity of air from 2.98 to 3.92g/㎏DA, air velocity from 1 to 2m/s, and cooling surface temperature from -5 to -15℃. The coolant was 50% ethylene-glycol aqueous solution. Frost surface temperature was decreased and frost thickness was increased near the tube side of the fin-tube arrangement. Frost temperature profiles on the fin side were fully scanned. Heat transfer rate was increased up to 30 minutes and the decreased as the frost thickness was thickened as time passes.