이산화탄소/프로판 혼합냉매의 냉방성능에 대한 충전량의 영향 및 순환성분비 변화 특성

김주혁, 황윤욱, Min-Soo Kim · 설비공학논문집 · 2006

CO₂ and propane mixtures, which are environmentally benign, nontoxic, low in price, and compatible with materials and lubricants, were considered as promising alternative refrigerants. A fully instrumented air-conditioning system was developed for a precise performance evaluation of pure CO₂ and CO₂/propane mixtures. In this paper, the effect of the charging amount and circulation concentration on the cooling performance of the system using CO₂ and propane mixtures was tested and discussed. Pure CO₂ and 85/15, 75/25 and 60/40 binary blends by the charged mass percentage of CO₂/propane were selected as working fluids. An optimum charging amount was proposed as a parameter instead of the degree of subcooling, which can not be well defined in the transcritical cycle, to properly compare the performance between the transcritical and subcritical cycles.

Cited by 0 works.