착상 조건에서 핀피치에 따른 특성 비교

김정근, 황지은, 조금남 · 대한설비공학회 학술발표대회논문집 · 2013

Present study aimed to measure frost characteristics and heat transfer rate of fin-tube heat exchanger of heat pump with respect to fin pitch under frosting condition. The test conditions were air temperature of 2℃, absolute humidity of 3.67 g/kgDA, air velocity of 1.5 m/s, and coolant temperature of -10℃. The coolant was ethylene-glycol aqueous solution with concentration of 50%. The performance of large fin pitch of the flat plate was better about 10% than that of low. But the performance of 1.3mm was the best in case of the louver fin.

Cited by 0 works.