국내 업무시설에서 능동형 칠드빔 시스템의 적용방법에 따른 에너지성능 분석

우지혜, 엄태윤, 연창근 · 대한설비공학회 동계학술발표회 논문집 · 2014

The purpose of this study is to analyze the energy performance on the difference between the applied methods of chilled beam systems in a office building, Korea. As a result, the energy savings rate of the active chilled beam systems with passive dehumidification wheel(ACB(+PDW)) was 32% compared with VAV reheat systems(VAV), and energy savings rate of ACB(+PDW)&VAV was 26% compared with VAV. In case of office space that SHF was more than 0.8, the energy growth rate of the ACB&VAV was 6% compared with ACB(+PDW)&VAV: the cooling energy increase by 1%, the heating energy increase by 37%. That is, it was shown that the ACB with PDW in office space was useful for energy saving.

Cited by 0 works.