자연냉매의 마이크로 휜관 증발열전달 및 압력강하 특성
오승택, 이호생, 백승문 et al. · 대한기계학회 춘추학술대회 · 2008
This paper presents the heat transfer and pressure drop characteristics of R-290 (Propane), R-600a (Iso-butane) and R-1270 (Propylene) as an environment friendly refrigerant and R-22 as a HCFC's refrigerant for evaporating. The test section is a horizontal double pipe heat exchanger. Evaporating heat transfer and pressure drop measurements were performed for 12.70, 9.52 mm micro-fin tube and compared with the results in smooth tube. The local evaporating heat transfer coefficients of hydrocarbon refrigerants were superior to those of R-22 and the maximum increasing rate of heat transfer coefficient was found in R-600a. The average evaporating heat transfer coefficients in hydrocarbon refrigerants showed 8.94 to 13.36% higher values than those of R-22. Hydrocarbon refrigerants have a higher pressure drop than that of R-22 with respect to refrigerant quality and mass flux. Also, the evaporating heat transfer coefficient and pressure drop of working fluids in smooth and micro-fin tube were compared. The heat transfer enhancement factor (EF) and penalty factor (PF) between smooth and micro-fin tube varied from 2.1~2.5 and 1.49~1.61 in all experimental conditions, respectively.