음향 시뮬레이션을 이용한 댐 수차 발전기실의 음향성능 개선
정은정, 최둘, 김재수 · 대한건축학회 학술발표대회 논문집 - 계획계 · 2007
As Waterpower Generation generates electricity using the difference of altitude of water, also let the turbine revolves through water pipe, at this time the revolving turbine causes exceedingly huge noise. Accordingly, not only those workers in the hydraulic turbine dynamo room are suffering the difficulties in mutual communication, but also those workers in the adjacent office are enduring the obstruction to the business due to the noise. Particularly, since the dynamo room located on the middle between the hydraulic turbine dynamo and the office had been architecturally concluded, not only with all of the reflection materials, but also holds a great volume of 22,800㎥, it functions rather to amplify the Noise that occurs during the operation time of the hydraulic turbine dynamo. Accordingly, after actually measure the architectural acoustic performance on the object of the hydraulic turbine dynamo room, and compare with the forecasted value through a computer simulation, thence this Research has verified the authenticity of the simulation. Based on such authenticity of the forecasting, this Study would intend to propose the architectural acoustic element likely as restraint the amplification of dynamo noise, reduction the noise travelling to the adjacent room, enable to maintain the optimum acoustic condition.
Cited by 0 works.