전원 불평형시 능동전력필터의 해석 및 제어기에 관한 연구
김응진, 조준석, 최규하 et al. · 전력전자학술대회논문집 · 2000
Active power filters are used to compensate reactive and harmonic CUITent on nonlinear loads. And to improve compensation characteristics of achve power filter systems, the accuracy of harmoruc currents detector and the deSIgn of CUITent controller are important In special under unbalanced condihon, nonlinear loads include low order harmonic CUITents (like 1st and 2nd order) on the synchronous reference frame due to negative sequence CUITent. Therefore Because of the bandwidth characteristic of LPF, detection of harmonic cUITents by conven1:1onal lowpass filter are maccurate. In this paper, to solve the defect of LPF for detection of CUITent under unbalanced condition, we propose the MAF(Moviing Average Filter) which has high accuracy. This MAF is consist of lowpass and bandstop filter charactenstic that remove all of harmonics. And proposed method and theoretical result are verifIed by sImulation and expenment.
Cited by 0 works.