기존 국내의 칼럼-트리 형식 접합부 철골모멘트 골조의 내진성능평가
이강민, 오근영, 진유의 et al. · 대한건축학회 학술발표대회 논문집 · 2013
The 'column-tree' steel moment frame has been widely used in korean whose beam-column connection was welded in the shop and the beam splice was bolted in the field. In the study, strong-axis and weak-axis connection were experimentally evaluated using the connection detail before Northridge earthquake. As a result, both of the connections were shown to have more than 4% story drift ratio and have brittle failure at the root of beam flang at 4% story drift ratio. Bolt slip was also occurred. The failure mode was the same as that in Nothridge earthquake. Based on the experiment result, it was considered that connection detail and retrofit method should be more needed to meet seismic design.
Cited by 0 works.