액체저장탱크의 내풍압, 내진 설계 기준 평가

박종률, 오택열 · 대한기계학회 춘추학술대회 · 2003

Evaluation for basis on wind pressure design and seismic design of liquid storage tanks specified in KS B 6225 and Fire Protection Law in Korea is present. The basis on wind pressure design and seismic design is modified to meet the environmental condition in Korea. Equations for calculating wind pressure and recommended wind design procedure of the tanks are presented. The basis for establishing design loads due to hydrodynamic pressure is described including seismic zone risk map in Korea, zone coefficients and the essential facilities factor. This procedure for calculating applied compressive stress on the shell base subjecting to seismic load and for estimating the allowable buckling stress is described.