태양열 이용 냉난방 공조시스템의 재생성능에 영향을 미치는 인자의 기여율에 관하 ㄴ연구
김보철, 최광환, 금종수 · Journal of the Korean Solar Energy Society · 2000
This study was performed to find out how much experimental factors influence on regeneration performance in a solar air conditioning system. The experimental apparatus was set up in a climate-controlled chamber where temperature and humidity could be kept constant. In order. to investigate factors' influence on the regeneration performance of the solar air conditioning system, the model experiment was done using the 600mm x 600mm black painted aluminum regenerator. The design and analysis of experiment were done by the design of experiments, especially the table of orthogonal arrays. In order to find out how much experimental factors influence on regeneration performance, the table of orthogonal arrays L_8(2^7) was used. According to the results, it was found that the most influential factor to affect regeneration performance was the concentration of LiCI solution. The next influential factors were a solar radiation, an air velocity, and the temperature of LiCI solution in order.
Cited by 0 works.