회로의 과도해석방법을 이용한 수직밀폐형 지중열교환기의 해석 연구

김원욱, 박홍희, 전종욱 et al. · 대한기계학회 춘추학술대회 · 2009

Most of ground coupled heat pump systems are usually controlled by ON/OFF control of a heat pump with typical cycling frequencies of 1-4 cycles per hour. The start up losses (cycling losses) of heat pumps normally cannot be neglected. The transient behavior of the system in Short time steps might be calculated' properly when we design and analyze a ground coupled heat pump system. It is important that the model of a vertical ground heat exchanger (GHEX) is able to predict the transient behavior correctly. Several numerical or analytical models have been proposed to analyze the thermal response of the vertical GHEX. Most of the models are valid after few hours of operation since they neglect the heat capacity of the borehole. In this paper, we present a simple algorithm to evaluate Short time step responses of the GHEX. This paper focuses primarily on the simplifications and modifications of the dynamic borehole model (TRNSYS Type 451) by using analogy of electric circuit transient analysis.

Cited by 0 works.

Authors