강의실 냉방시 열쾌적성 및 실내공기질 연구

노광철, 장재수, 오명도 et al. · 대한기계학회 춘추학술대회 · 2005

The experimental and the numerical study was performed on the comparison of thermal comfort(TC) and indoor air quality(IAQ) in the lecture room for cooling loads when the operating conditions are changed. PMV value and CO² concentration of the lecture room were measured and compared with the numerical results. The numerical results showed a good agreement with the experimental one and then the numerical tool was used to analyze thermal comfort and IAQ for a couple of operating conditions. As a result it was found that the increment of the discharge angle of system air-conditioner makes TC uniformity worse, but rarely affects IAQ. Also TC and IAQ were hardly affected by the variation of the discharge airflow. Finally it turned out that TC is merely affected by the increment of the ventilation airflow, but the average CO² concentration can be satisfied with Japanese standards when the ventilation airflow is more than 800CMH in this study.

Cited by 0 works.