터널화재시 연기제어에 관한 실험적 연구
이성룡, 김충익, 유홍선 et al. · 대한기계학회 춘추학술대회 · 2002
In this study, reduced-scale experiments were conducted to analyze smoke movement in tunnel fires according to ventilation method. The 1/20 scale experiments were carried out under the Froude scaling using gasoline pool fires ranging from 6.6 to 10 em in diameter corresponding to total heat release rate from 0.714 to 2.5 kW. Temperatures near the ceiling were lowered by installing the vent, and more lowered by operating fan than for the tunnel without vent. In case of forced ventilation, the exhaust fan was more effective than the suction fan. Vertical temperatures at the upper part of the tunnel were also lowered by installing the vent. But, when suction fan was operated, temperatures at the lower part of the tunnel were higher than that without vent.