논문 : 목재연소시의 실내화재성상과 안전대피시간
정길순, 태순호, 이병곤 et al. · 1993
Available Safe Egress Time(ASET) is the time available for occupants to evacuate safely in compartment fire, and it depends on the time of fire detection and hazardous conditions. The purpose of this study is to provide an analytical basis and experimental data for estimating the fire growth in compartments and the available safe egress time, and to compare the experimental data with those proposed equations. As a result, hazard order is poison to CO, descent of smoke layer, poison to CO₂, burn to hot smoke layer, and lack of O₂, ASET is lengthened in this order. Also, The more fire load is increased, the more ASET is shorted.
Cited by 0 works.