천장 복사 냉방 패널의 단열 및 설치 형태가 거주역의 공기 온도에 미치는 영향

신미수, 여명석, 김광우 · 대한건축학회 학술발표대회 논문집 · 2015

The cooled radiant ceiling panels have been installed in the form of closed ceiling type with the insulation on the upper surface of panels since the cooling heat flow on the upper surface of panels seems to be helpless to remove the cooling load in the occupied zone. In this study, through the CFD simulation, it is demonstrated that the heat flow on the upper surface without insulation can reduce the occupied zone air temperature in some cases. In addition, the panels arranged with openings lead to the lower air temperature in an occupied zone than that of the room with closed ceiling. It is because that the heat flow on the upper surface of panels cools the upper air and increases the density of the air, the cooled air comes down to the occupied zone through the opening.

Cited by 0 works.