전압강하에 따른 화재비상경보 설비음의 변동특성에 관한 실험적 연구

백건종, 신훈, 장길수 et al. · 한국건축친환경설비학회 학술발표대회 논문집 · 2009

In this study, voltage variation effects on sound level of fire alarm system were examined. Followings are results. Within the voltage band of ±20% from 24V(center) which is standard voltage, the sound pressure level is considered to be stable but in the condition of -20% below voltage dropping, adequate sound pressure level output is not anticipated. Acoustic equipment which is far from receiver can not fulfill standard sound pressure level output due to voltage dropping and this could cause a problem that fire alarm could not be heard to inhabitants.

Cited by 0 works.