이산화탄소 냉동사이클에서 사이클 사양에 따른 최적충전량 변화에 관한 실험적 연구

조홍현, 류창기, 이호성 et al. · 대한설비공학회 학술발표대회논문집 · 2005

The cooling performance of a transcritical CO₂ cycle varies significantly with a variation of refrigerant charge amount. In this study, the performance of the CO₂ system was measured and analyzed by varying refrigerant charge amount with a change of cycle option. The applied cycle options are the single-stage compression system, two-stage compression with 1-EEV system, and two-stage compression with 2-EEV system. The optimum normalized charge were 0.363, 0.297, and 0.282 for the two-stage compression with 2-EEV system, two-stage compression with 1-EEV system, and single-stage compression system, respectively.

Cited by 0 works.