수계소화장치용 수리계산 기준에 대한 고찰
이경우, 김만용, 김유택 et al. · 한국마린엔지니어링학회 학술대회 논문집 · 2004
The fire extinguishing capability of water-based fire extinguishing system largely depends on the pressure at nozzles. Hence, the pressure at nozzles is the most importance element to consider in the design work. Since it is difficult to perform the discharge test to confirm the pressure at nozzles, the hydraulic calculation is used to verify the pressure. To perform acceptable hydraulic calculation, there is a need to provide accurate hydraulic calculation standard. Such standard is the NFPA Code 750. In the Code, two flow energy loss calculation methods Darcy-Weisbach equation and Hazen-Williams equation - are prescribed. In this paper, the correlation of two calculation methods are reviewed and the hydraulic calculation standard for water mist extinguishing system is proposed.
Cited by 1 works.