제주 해수열원 이용 냉난방 성능운전에 관한 실증연구
김기봉, 이길봉, 나호상 et al. · 대한설비공학회 2015년도 하계학술발표대회 · 2015
The purpose of this study is to investigate the filed operation characteristics about cooling & heating system using sea water source in Jeju. The capacity of demonstration plant which was built in JGRC is about 20RT. The demonstration plant is available for operation of cooling and heating seasonally. The field Test results show that the cooling & heating system using sea water source exhibits a COPc of between 2.9∼3.4 in cooling mode along with a COPh of between 3.2∼3.52 in heating mode.
Cited by 0 works.