진동형 히트파이프 형상에 따른 배기열 회수장치 성능에 관한 연구

구연우, Sang Il Lee, 권용하 et al. · 대한설비공학회 2013년도 하계학술발표대회 · 2013

In this study, we developed and tested Pulsating Heat Pipe(PHP) type Exhaust Heat Recovery System(EHRS) for high temperature and humidity environment. Experiment performed by varying the charging ratio, number of PHP module, length ratio of condensation and evaporation part and type of heat exchangers. Working fluid is R-134a. In previous study using flat-tube heat exchanger, efficiencies of temperature and enthalpy are highest when charging ratio is same with length ratio of condensation and evaporation part. In this study, AHU exchanger is used instead of the flat-tube heat exchanger. Consequently, Efficiency of PHP using flat-tube heat exchanger is higher than using AHU heat exchanger.