버블 유동층과 스펀지 볼을 이용한 폐수열회수 히트펌프 시스템 증발기의 파울링 저감 장치에 관한 연구
김도빈, 김준하, 김종수 · 대한설비공학회 동계학술발표회 논문집 · 2015
Waste water heat recovery heat pump system uses heat of waste water from public bath or factory as heat pumps heat source. This system uses a bare tube evaporator. Most Thermal resistance is caused by fouling which occur in outer surface of evaporator. Formed fouling increases directly thermal resistance between waste water and refrigerant so this decreases heat pumps efficiency. In this study, we fabricate fouling mitigating device in recovery heat exchanger using fluidized bubble with sponge ball. Experimental condition is as follow : cold water temperature is 20℃, waste water temperature is 40℃, cold water flow rate is 100kg/h and heat exchanger surface area is 0.161m2. As a result, thermal resistance by formed fouling used fluidized bubble and sponge ball was lower than if not. When the number of sponge balls was higher, thermal resistance was lower. However, when the number of sponge ball was higher than 300, amplitude of thermal resistance decrease was lower.
Cited by 0 works.