영상 전류를 이용한 변류기 개방 판단 알고리즘
강용철, 이병은, 이현웅 et al. · 대한전기학회 학술대회 논문집 · 2006
A current differential relay has been used for transmission line protection. The relay may maloperate in the case of a failure of the secondary circuit of a current transformer (CT) because the differential current is produced. This paper presents an algorithm to detect a failure of a CT using the zero-sequence current. If the magnitude of the zero-sequence current is the same as the magnitude of the current of the other healthy phases, a failure of a CT is detected and then the blocking signal is activated. The proposed algorithm prohibit the maloperation of a differential relay in the case of a CT failure and thus increase the security of the relay.