흡수식 냉온수기용 용액열교환기 특성실험
Phan Thanh Tong, 임종극, 문춘근 et al. · 2000
Recently, growth of industry and progress of living quality came to need more electric power in summertime. Restraint on the materials such as CFC, CO₂, SOx and NOx became severe. Absorption chiller/heater can solve these problems successfully because natural gas is one of the clean energies and is able to supplied stably. It was built and tested for solution heat exchanger in absorption chiller/heater. Experiment was done with a solution heat exchanger which tube is installed by a promotor inserted tube and a spiral tube. It was tested that the overall heat transfer coefficient, pressure drop were researched by variation of solution flow rate. The overall heat transfer coefficient of the promotor inserted tube in solution heat exchanger is higher than that of spiral tube. But in case of the pressure drop in tube, the spiral tube is lower than the promotor inserted tube.