대구경 원관이 적용된 웨이브 휜-관 열교환기의 공기측 성능
이을종, 풍익, 심용섭 et al. · 대한설비공학회 동계학술발표회 논문집 · 2012
In this study, air-side performance of wave fin-and-tube heat exchangers having large diameter(12.7mm, 15.9mm) tubes was investigated. Eight samples having different tube rows were tested. For both configurations, the effect of tube row on j-factor was negligible. However, f-factor increased as the tube row decreased. The j-factor and f-factor of the tube diameter 12.7mm sample were approximately 32% and 26% higher than those of 15.9 mm sample.
Cited by 0 works.