고압전동기 운전중 부분방전 추이 분석

김희동, 공태식, 깅충효 · 대한전기학회 학술대회 논문집 · 2006

During normal machine operation, partial discharge(PD) measurements were performed with turbine generator analyzer(TGA) in two high voltage motors(rated 6.6 ㎸). These high voltage motors were installed with 80 pF capacitive couplers at the terminal box. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude (Qm). The trend analyses of NQN and Qm value are available for monitoring of the insulation condition in stator windings of high voltage motors.

Cited by 0 works.