루버핀관 열교환기의 서리 특성 및 전열 성능 예측

임진아, 박원걸, 조금남 · 대한설비공학회 학술발표대회논문집 · 2015

Frost is formed on the louvered fin tube heat exchanger of heat pump when moist air temperature below 0℃ is flowing over its cold surface. Formed frost acts as a thermal resistance to make heat transfer rate decrease and blocks air flow space to increase air side pressure drop at the heat exchanger. Frost prediction on the heat exchanger leads how to delay frost in order not to increase defrosting energy. Frost pattern on the heat exchanger was predicted by using segment by segment method for the heat exchanger. Local heat transfer rate for each segment was obtained by applying e-NTU method. The proposed model was validated by comparing the predicted values with the measured data for the frost on the louvered fin tube heat exchanger under the frost condition. Predicted local and average frost thickness, average air side pressure drop, and heat transfer rate agreed with the measured data within ±18.9%.

Cited by 0 works.