하이드로카본계열 순수 냉매의 외부 응축열전달계수에 관한 연구

채수남, 배동수, 정동수 et al. · 대한설비공학회 학술발표대회논문집 · 2002

The condensation of pure hydrocarbon-refrigerants on the outside of smooth tube, low-fin, Turbo-C were studied. Tested refrigerants were CFC, HCFC, HFC series of R11, R12, R22, R123, R134a, R32 and hydrocarbon series of Propane(R290), Propylene(R1270), D.M.E.(Dimethylether;(CH₃)₂O), N-Butane(R600), Iso-Butane(R600a). The HTCs were experimentally determined using a test section composed by those tested tube at the vapor temperature 39℃ with the wall subcoolings of 3~8℃. Nusselt's correlation for a smooth tube under-predicts 5.8~12.6%, average 8.1% deviation for all smooth tube data. While Betty-Katz's correlation for low fin tube also under-predicts 3.7~19.6%, average 9.9% deviation for all low fin tube data. And for all refrigerants, low fin tube and Turbo-C tube data results enhanced higher about 5.2 and 6.8 times than smooth tube data.