단순 핀-관에서의 착상 측정

곽동근, 이윤석, 조금남 et al. · 대한설비공학회 학술발표대회논문집 · 2010

The present study measured the frost characteristics on an array of fin-tube under the heat pump condition. The key test conditions were air temperature of 2℃, absolute humidity of 3.67 g/㎏DA, air velocity of 1.5 m/s, and coolant temperature of -10℃. The coolant was ethylene-glycool aqueous solution with the concentration of 50%. Total frost mass was measured by increasing the number of fin. Local frost mass was increased near the tube side of the fin-tube arrangement. Frost mass profiles on the fin side were monitored. Heat transfer rate was increased up to 30 minutes and then decreased as time passes.