수액기 유무에 따른 히트펌프시스템의 성능 비교에 관한 연구

조기현, 고광수, 박윤철 · 대한설비공학회 2015년도 하계학술발표대회 · 2015

A system was installed for the performance test of the Water cooling Heat pump system for Fuel cell electric vehicle according to whether the Receiver tank. Fixing the compressor speed to 1800rpm, and the Expansion valve was using 1.5RT EEV, the opening EEV set 100%, and the Refrigerant charge was set to experiment with 1100g, 1200g, 1300g, and when the Receiver tank of 1RT was setting or not, in two ways was tested. When Air source the COP increased from 2.83 to 3.97, when Air Preheater source increased from 4.64 to 4.65, when Water source increased from 4.77 to 5.84. When the Receiver tank was installed and the Refrigerant charge was 1200g, COP was measured up to 6.09.

Cited by 0 works.