습도에 따른 전열교환기의 성능 변화에 관한 연구

이을종, 송길섭, 오왕규 et al. · 대한기계학회 춘추학술대회 · 2009

Effect of air humidity on thermal performance of a enthalpy exchanger was experimentally investigated. The apparatus was specially-made to accurately measure the incoming and outgoing dry and wet bulb air temperatures as well as flow rates. Tests were conducted varying outdoor humidity. It is shown that latent heat exchange effectiveness is solely dependent on absolute humidity. The latent heat exchange effectiveness increases with the increase of absolute humidity. The water vapor permeability of the paper membrane was separately measured, and it is found that the permeability also increases with the increase of absolute humidity. Sensible heat exchange effectiveness is independent of both temperature and humidity.

Cited by 0 works.