다분지 시스템의 냉매 분배 특성에 미치는 분지관 내 변수 영향도에 관한 연구
태상진, 조금남 · 대한설비공학회 학술발표대회논문집 · 2002
The present study investigated the parameter effect on the flow distribution characteristics of refrigerant in branch tube. The experimental parameters were the orientation of inlet and branch tubes(horizontal, vertical upward and downward), the mass flux of inlet tube (200-500 ㎏/㎡s) and inlet quality (0.1-0.4). The parameter effect for each geometric and dynamic parameters was compared with the mass distribution ratio under fixed conition. The flow distribution ratio changed within -46% to 28% as the direction of branch tube changed, and within -14% to 32% as the direction of inlet tube changed. It also varied within -12% to +9% as the inlet mass flux and quality changed. The quality at the branch tube increased rapidly as the direction of branch tube was changed from horizontal to vertical upward. The effect of change direction of inlet and branch tube on the flow distribution and phase separation characteristics was more significant than that of dynamic parameters.
Cited by 0 works.