외기부하와 연동한 환기장치의 제어에 관한 연구
김태호, 유성연, 한규현 et al. · 대한기계학회 춘추학술대회 · 2012
As the modern buildings are gradually air-tightened for energy saving, the important of ventilation is increasingly being emphasized. The purpose of this study is to develop ventilation control method considering outdoor cooling/heating loads as well as indoor air quality. Two control methods, control of allowable CO₂ concentrations and control of fan flow rates, are investigated and the results are compared. Allowable concentrations are adjusted using a ON/OFF control, and fan flow rates are controlled using a fuzzy algorithm. Comparing with the existing control method, a little increase of CO₂ concentration is found, but more than 10% of energy is saved. If the appropriate correction of fuzzy rule is made depending on the site, more positive results could be obtained.