Контроль настройки компенсации емкостных токов с наложением вспомогательного тока через типовой трансформатор напряжения

Роберт Александрович Вайнштейн, Н. В. Коломиец, Н Р Пономарчук · Современные проблемы науки и образования · 2015

An implementation of control method of the detuning compensation degree of capacitive currents in medium voltage electrical power system (6-35 kV) based on introduction of residual-current circuit at nonindustrial frequency is described in this paper. In the proposed method the connection of the source of nonindustrial frequency is carried out via the secondary circuit of the voltage transformer, while measuring of nonindustrial frequency value is carried out via low-voltage current transformers connected to ground. The electrical signal produced by this device can be used both for visual controlling of the detuning compensation degree and automatic setting of ARC–suppressing reactors. The above mentioned approach can be used in electric power system with combined neutral grounding where the value of total relative conductance in zero-sequence scheme equals up to 20%. Additional absolute measurement error of the detuning compensation caused by increased conductivity does not exceed 0.9%.

Cited by 0 works.