데이터 센터 외기냉방 최적 운전제어 알고리즘 개발 및 효과 분석
황지현, 한기성, 이태원 · 대한설비공학회 2015년도 하계학술발표대회 · 2015
Recently electric power consumption at data center has been increasing very steeply with the rapid spread of internet network and a fast evolution of information and communication technologies. Outdoor air cooling system could be used for cooling the indoor space with relatively cold outdoor air which led to save cooling energy and cost. As results, only the cases of M, MW and W, among 5 weather conditions considered, expected to be able to remove heat with outdoor air cooling system. It was proved that the outdoor air cooling was applicable in case of daily averaged outdoor air temperature higher than 24℃. The all of heat generated in space could be removed by outdoor air cooling, which yielded energy and cost saving over 90%.