차양의 표면 반사율에 따른 사무소 건물의 냉방부하 분석 연구
최선우, 한설이, 박효순 et al. · 한국생태환경건축학회 학술발표대회 논문집 · 2011
Currently, most wall of the office buildings has been applied to the curtain walls. Curtain walls have the advantage that is securing a clear view and reducing a lighting load depending on transmissivities. In case of the summer, a cooling load increased due to get the solar energy through the curtain walls. For this reason, the research has proceeded about improving the thermal performance of the curtain walls or installing the shading device. A lot of the research was only considered lengths of the shading devise and installation angle. Depending on the surface reflectance rate, solar radiant energy is different. The aim of this study is to analyze the cooling load effects of shading device through the simulations, depending on the shading device of different surface reflectance rate. For the study, office building with the curtain walls of south was designed. It was each calculated cooling load by using a computer simulation program; EnergyPlus depending on the shading device with different surface reflectance rate or not. as a result, in case of the shading device with surface reflectance rate of 20% cooling load decreased by 5.93% than basic case. In case of increasing surface reflectance rate per 10%, cooling load was increased mean per 0.53%.
Cited by 0 works.