시설원예용 열펌프시스템의 팽창밸브 변경에 따른 성능특성에 관한 연구

송뢰, 고광수, 박윤철 · 대한설비공학회 2015년도 하계학술발표대회 · 2015

In this experiment, in order to determine the amount of refrigerant filling and evaluate the COPh performance of heat pump system by changing the expansion valve. We increased the expansion valve capacity from 1.5RT to 3.0RT, and replaced EEV with TXV to conduct the experiment. Basic experimental conditions were as follows, in indoor conditions, dry-bulb temperature was 20℃ and wet-bulb temperature was 15℃, air volume was 8㎥/min, and in outdoor conditions, dry-bulb temperature was 7℃ and wet-bulb temperature was 6℃, air volume was 10㎥/min. When EEV(1.5RT) opening degree was 100%, the amount of refrigerant filling was 1,300~1,400 g, the performance of the system was the best. Between the EEV(1.5RT) opening degree was 100% and EEV(3.0RT) opening degree was 25%, the amount of refrigerant filling was the biggest. When EEV(3.0RT) opening degree was 25%, COPh was the highest.