공동주택 세대별 난방제어 알고리즘 개선에 관한 연구
서정아, Younggy Shin, 김용기 et al. · 대한설비공학회 동계학술발표회 논문집 · 2015
Most of hot water heating valves for apartments are constant-flow type, which limits flow rate through an individual household for even distribution of heating water to other households. The constant-flow type is implemented by on-off control. As a result, heating water is supplied intermittently and hence indoor air temperature is also fluctuated. And returning water temperature is also high, which deteriorates exergy efficiency. To implement continuous feedback control, the indoor temperature dynamics was simulated to fit in measured temperature history by an state-of-the-art physical model. From the model, it was found that the most important disturbance is outdoor temperature and its effect on indoor temperature takes about an hour. To cope with the slow response and the significant disturbance, a prediction control with proportional feedback is proposed. The is found to be successful in implementing continuous heating water flow along with improved indoor temperatrue quality.