보육시설 적용 지열히트펌프시스템의 하절기 운전특성 및 에너지성능 실증평가
고명진, 김용식 · 한국생활환경학회지 · 2015
To spread the application of ground source heat pump (GSHP) systems, this paper carried out empirical evaluation of operation characteristics and energy performance of the GSHP system. The GSHP considered in this study has a cooling capacity of 89.7㎾ and a heating capacity of 93.5㎾, and coefficient of performance (COP) in cooling mode of 4.7 and COP in heating mode of 3.5. From the monitoring results in summer season, it was observed that average daily temperatures of liquid entering the load side of the GSHP were measured to be 9.5℃, 8.7℃ and 10.1℃ in typical day from June to August that were sufficient to ensure proper cooling to the building. In the same days, average daily temperatures of liquid entering the source side of the GSHP were measured to be 17.56℃, 20.1℃ and 21.5℃. Although the temperature was increased about 4℃ due to the continued cooling operation of approximately 3 months, it was still lower than 25℃ generally evaluated as stable operation condition in cooling mode. In addition, it was found that the GSHP system shows a high energy performance because average COP and system COP for analysis period were computed at 7.1 and 4.4 higher than the nominal value, respectively.