직교ㆍ대향류 하이브리드 냉각탑의 성능특성에 관한 연구

장걸, 김은필, 전철호 et al. · 한국동력기계공학회 학술대회 논문집 · 2005

The performance of cooling tower is dependent on the thermal performance of the packings. It's assessed by measuring packing characteristic values and pressure drops. In this study, a hybrid fill packing cooing tower is developed by combining the counter flow type fill packing with the cross flow type fill packing. Numerical investigation on the hybrid fill packing cooling tower has been done preliminary to experimental investigation. The result shows that cooling capacity on the hybrid fill packing cooling tower is higher than existing counter and cross flow type cooling tower as the experimental study. But The pressure drops on hybrid fill packing cooling tower are about 20% higher than other type cooling towers.

Cited by 0 works.