가우시안 포락선 선형 첩 신호의 순시 주파수 추정을 통한 원전 내 계측 케이블의 고장점 진단 연구
이춘구, 박진배, 윤태성 · 2013
Integrity of the control and instrumental cables in nuclear power plant is important to maintain the stability of the nuclear power plants. In order to diagnose the integrity of the cables, the diagnostic methods based on reflectometry have been studied. The reflectometry is a non-destructive method and it is applicable to diagnose the live cables. We introduce a Gaussian enveloped linear chirp reflectometry to diagnose the cables in the nuclear power plants. In this paper, we estimate the instantaneous frequency of the Gaussian enveloped linear chirp signal by using the weighted robust least squares filtering to localize the impedance discontinuities in the class 1E instrumental cable.
Cited by 0 works.
Authors
References
- Frequency-domain reflectometery for on-board testing of aging aircraft wiring
- Application of Time-Frequency Domain Reflectometry for Detection and Localization of a Fault on a Coaxial Cable
- A Model-Based Probabilistic Inversion Framework for Characterizing Wire Fault Detection Using TDR
- Recursive Weighted Robust Least Squares Filter for Frequency Estimation
- 무손실 영상 압축을 위한 변형된 정수 변환 계수에 대한 순방향 적응 예측 기법
- Fiber-optic Goniometer to Measure Knee Joint Angle for the Diagnosis of Gait Disturbance
- Fast time-frequency domain reflectometry based on the AR coefficient estimation of a chirp signal
- Partial Discharge Measurement of Power Cables for Nuclear Power Plant