This study aims to evaluate appropriate capacity of the ventilation system for improvement of indoor air quality in classroom. To this end, we measured the indoor air quality of the classroom by categorizing schools into elementary school, middle school and high school. The measurement of the indoor air quality of the classroom is proceeded during heating when the class is being held in the classroom and after the ceiling inverter cooling and heating system is operated with the openings closed according to whether the ventilation system is operated or not and the variation of the amount of ventilation. The main results of this study are summarized as follows; The required amount of ventilation should be decided not by the contaminants(HCHO and TVOC) emitted from the construction materials but by CO2 emitted from human breath. Considering the current education courses, the appropriate capacity of the ventilation system of the classroom for elementary school is considered reasonable to be 500CMH and for middle and high schools 800CMH. The difference between the measured value and the estimated value of modeling the CO2 concentration of the classroom for elementary schools was analyzed to be 148ppm and for middle schools 545ppm and the estimated value was lower than the measured one.