배전계통의 전압안정화를 위한 선로전압조정장치와 전지전력저장장치의 협조제어 알고리즘에 관한 연구

김병기, 왕종용, 박재범 et al. · 2016

In order to maintain customer voltages within allowable limit(220±13V) as much as possible, tap operation strategy of SVR(Step Voltage Regulator) installed in distribution system is very important, considering the scheduled delay time(30 sec) of SVR. However, the compensation of BESS(Battery Energy Storage System) during the delay time of SVR is being required because the customer voltages in distribution system interconnected with PV(Photovoltaic) system have a difficultly to be kept within allowable limit. Therefore, this paper presents the optimal voltage stabilization method in distribution system by using coordination operation algorithm between BESS and SVR. It is confirmed that customer voltage in distribution system can be maintained within allowable limit(220±13V).

Cited by 0 works.

Authors