동시냉난방 시스템 에어컨의 고낙차 장배관 운전 신뢰성 평가
김태안, 이승찬, 문제명 et al. · 대한설비공학회 하계학술발표회 논문집 · 2008
The heating and cooling performance of system multi-air conditioner under high-head and long-line conditions are experimentally investigated. The maximum head and tube length were 110 m and 1000 m, respectively. The experimental system was composed of 4 outdoor units with module systems, and 13 indoor units which were joined with the mode change unit by single-tube circuit. Field tests without indoor and outdoor temperature control were performed in a general office building with 22 different working conditions. Experimental results were prepared on the p-h diagram. Also the oil level in the compressor was normally maintained at the safety zone for the system multi-air conditioner with high-head and long-line conditions.
Cited by 0 works.