단락전류에 의한 고압전동기 단자박스부 절연애자의 구조안전성 평가

박윤범, 손락원, 김주필 · 대한기계학회 춘추학술대회 · 2015

In order to avoid failure of the 50kA short circuit current for insulator of high voltage motor’s terminal box during working process, the structural safety of insulator has been investigated by using Electromagnetic-Structure couple module of commercial FEM code, Maxwell and ANSYS. Maxwell is used to calculate the body forces caused by short circuit current under various conditions. In the structural analysis, Dynamic effect coefficient of impulse length ratio is used to convert the steady state results to the transient results. As a result, it has been secured about structural safety for insulator of high voltage motor’s terminal box.