전도열손실이 재생증발식 냉각기 성능에 미치는 영향

박민희, 문승재, 이대영 · 대한설비공학회 2015년도 하계학술발표대회 · 2015

The regenerative evaporative cooler is a kind of indirect evaporative cooler comprised of multiple pairs of dry and wet channels. The air flowing through the dry channels is cooled without any change in the humidity and at the outlet of the dry channel a part of air is redirected to the wet channel where the evaporative cooling takes place. The smaller size of the heat exchange is, the more important conduction effect becomes. because temperature gradient is large by inlet and outlet temperature difference of high effectiveness heat exchange. It cause axial-conduction loss through wall and fin as a result, cooling effectiveness is reduced. In this study, the effects of axial-conduction loss on the cooling performance are investigated analytically. The cooling process in a regenerative evaporative cooler is modeled into a set of differential equations of added conduction term and solved analytically to obtain relation of effectiveness, conduction and NTU in the evaporative cooler. Based on the relation, it is analyzed how much the cooling performance is affected by the axial-conduction loss.

Cited by 0 works.