히트펌프 유닛 멀티 성능 데이터 기반 건물 통합형 히트펌프 시스템 년성능 평가 기법

강은철, 민경천, 이의준 · 대한설비공학회 학술발표대회논문집 · 2015

Heat pump unit performance is calculated by the one point design condition according to KS C 9306. However, when heat pump operated to the real buildings, it is changed continuously according to the actual weather conditions, the building load and heat pump source conditions. Therefore, the key parameters related to the building integrated heat pump system have to be considered properly by seasonal performance factor so called as SPF with multi-performance data points. The purpose of this paper is to evaluate the APF for a climate dependent building integrated air-to-air heat pump system in main cities in Korea. TRNSYS simulation tool with an international standard based on IPMVP 4.4.2 was utilized to perform the annual performance analysis. Seven major cities in Korea have been considered as the locations for residential building with 200m² floor area. Air-to-air heat pump system annual performance evaluation results were also performed by using Korea BIN data. APF from the BIN data method was calculated as 2.08. The APF with the multi-performance data based method was 2.29 for Daejeon residential building case. While Busan residential building case appeared as the highest with 2.36.

Cited by 0 works.